INERGEN SUPPRESSION SYSTEM

Published on Slideshow
Static slideshow
Download PDF version
Download PDF version
Embed video
Share video
Ask about this video

Scene 1 (0s)

INERGEN SUPPRESSION SYSTEM. PT ADIWARNA ANUGERAH ABADI.

Scene 2 (9s)

The Fire Tetrahedron. FUEL OXYGEN HEAT CHAIN REACTION.

Scene 3 (17s)

All-Natural Gases. 8 % CO 2. 40 % Ar. 52 % N 2. IG-541.

Scene 4 (20s)

15% O 2 LEVEL REQUIRED FOR COMBUSTION (FIRE). CO 2 LEVEL INCREASED TO ACCELERATE RESPIRATION.

Scene 5 (21s)

electric. paper. CLASS A ORDINARY COMBUSTIBLES. gas.

Scene 6 (1m 57s)

ADVANTAGE OF INERGEN SYSTEM. Tidak menghantarkan listrik Tidak meninggalkan sisa Bukan bahan yang bersifat korosi AMAN bagi manusia.

Scene 7 (2m 30s)

AGENT DISCHARGE. 4m 3m Im 100% Agent 100% Air Agent 100% Air.

Scene 8 (2m 50s)

SCHEMATIC.

Scene 10 (3m 28s)

. . . . . Manual Pull Station “Active” Active: Bell, Horn-Strobe & Warning Lamp SOLENOID ACTIVE INERGEN GAS DISCHARGE FACP System: Standby Status: Normal 1 Detector “Active” Bell Active Solenoid Mech. Actuator “Active” Reset Panel Abort Switch 2 Detector “Active” INTEGRATION SYSTEM BUILDING ALARM EXHAUST FAN AHU BAS False Alarm Delay Time Panel 30 Seconds.

Scene 11 (4m 36s)

. . . . . HOW SYSTEM WORKING. INERGEN fire extinguishing system dapat bekerja dengan 3 metode pengaktifan : 1. Auto: Aktif melalui deteksi “Detectors“ Detector secara otomatis aktif setelah mendeteksi sumber api (asap, panas atau lidah api ) dan selanjutkan akan mengaktifan system alarm kebakaran ..

Scene 12 (4m 38s)

. . . . . HOW SYSTEM WORKING. ,sct.øg. Standby. Active.

Scene 13 (5m 16s)

. . . . . HOW SYSTEM WORKING. 3. Manual Mechanical: Aktif dengan melalui "Manual Lever Actuator“ Cabut pin dan kemudian putar actuator searah jarum jam sebanyak ¼ putaran (30 degree). Solenoid akan aktif dan gas yang didalam cylinder akan otomatis discharge..

Scene 14 (6m 13s)

. . . . . Manual Release Reset. Stand By. Active.

Scene 15 (6m 42s)

Reset Alarm on the Panel  Hold Button ”SYSTEM RESET” and wait 30s till the warning lamp and the buzzer stop..

Scene 16 (7m 10s)

. . . . . Maintenance for Inergen. WHAT SHOULD BE CHECK? Cylinder  check the pressure Detector  check the condition (Cleanness) Ci IS8 Solenoid Actuator w/ manual  check the condition Nozzles  check the condition (cleanness).

Scene 17 (8m 27s)

. . . . . Maintenance for Inergen System. Schedule Requirement Monthly Inspect hazard area system components Check Inergen cylinder pressure Semi-Annually Check Inergen cylinder weight Test electric manous plug Annually Check inergen cylinder weight Blow out distribution piping Perform complete system function Test pneumatic detection system Every 5 years Hydrostatic test all inergen and system hoses and flexible connectors..

Scene 18 (8m 28s)

. . . . . THANK YOU.