INERGEN SUPPRESSION SYSTEM. PT ADIWARNA ANUGERAH ABADI.
The Fire Tetrahedron. FUEL OXYGEN HEAT CHAIN REACTION.
All-Natural Gases. 8 % CO 2. 40 % Ar. 52 % N 2. IG-541.
15% O 2 LEVEL REQUIRED FOR COMBUSTION (FIRE). CO 2 LEVEL INCREASED TO ACCELERATE RESPIRATION.
electric. paper. CLASS A ORDINARY COMBUSTIBLES. gas.
ADVANTAGE OF INERGEN SYSTEM. Tidak menghantarkan listrik Tidak meninggalkan sisa Bukan bahan yang bersifat korosi AMAN bagi manusia.
AGENT DISCHARGE. 4m 3m Im 100% Agent 100% Air Agent 100% Air.
SCHEMATIC.
. . . . . Manual Pull Station “Active” Active: Bell, Horn-Strobe & Warning Lamp SOLENOID ACTIVE INERGEN GAS DISCHARGE FACP System: Standby Status: Normal 1 Detector “Active” Bell Active Solenoid Mech. Actuator “Active” Reset Panel Abort Switch 2 Detector “Active” INTEGRATION SYSTEM BUILDING ALARM EXHAUST FAN AHU BAS False Alarm Delay Time Panel 30 Seconds.
. . . . . HOW SYSTEM WORKING. INERGEN fire extinguishing system dapat bekerja dengan 3 metode pengaktifan : 1. Auto: Aktif melalui deteksi “Detectors“ Detector secara otomatis aktif setelah mendeteksi sumber api (asap, panas atau lidah api ) dan selanjutkan akan mengaktifan system alarm kebakaran ..
. . . . . HOW SYSTEM WORKING. ,sct.øg. Standby. Active.
. . . . . HOW SYSTEM WORKING. 3. Manual Mechanical: Aktif dengan melalui "Manual Lever Actuator“ Cabut pin dan kemudian putar actuator searah jarum jam sebanyak ¼ putaran (30 degree). Solenoid akan aktif dan gas yang didalam cylinder akan otomatis discharge..
. . . . . Manual Release Reset. Stand By. Active.
Reset Alarm on the Panel Hold Button ”SYSTEM RESET” and wait 30s till the warning lamp and the buzzer stop..
. . . . . Maintenance for Inergen. WHAT SHOULD BE CHECK? Cylinder check the pressure Detector check the condition (Cleanness) Ci IS8 Solenoid Actuator w/ manual check the condition Nozzles check the condition (cleanness).
. . . . . Maintenance for Inergen System. Schedule Requirement Monthly Inspect hazard area system components Check Inergen cylinder pressure Semi-Annually Check Inergen cylinder weight Test electric manous plug Annually Check inergen cylinder weight Blow out distribution piping Perform complete system function Test pneumatic detection system Every 5 years Hydrostatic test all inergen and system hoses and flexible connectors..
. . . . . THANK YOU.